UPS Frequently Asked Questions (FAQs)


 

Do you have any information on UPS battery maintenance and storage?
Can the UPS battery be replaced?

Yes, all Acumentrics UPS units have user-replaceable batteries. If you require a new battery pack, please email the UPS (uninterruptible power supply) model number and your request to sales@acumentrics.com . A quote will be sent to you for the appropriate battery pack.

If you would just like the battery cells replaced, please email the UPS model number and the serial number of the battery pack to: repairs@acumentrics.com ; request a return authorization number and the cost for the repair.

For battery maintenance and storage information, please read the following:

For the ACG2500 Series UPS:

Maintenance and Battery Storage

The proper storage of UPS batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. This is called self-discharge. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. The self-discharge reaction rate increases as a function of temperature. If the batteries are stored long enough without a periodic replenishment of charge, an irreversible loss of battery capacity can occur, causing premature battery failure.

All Acumentrics battery packs are shipped fully charged. They should be stored separately from the uninterruptible power supply and used on a FIFO (First In, First Out) basis. All battery packs should be recharged before use of the UPS (uninterruptible power supply) if 100% capacity is required. The stored battery packs should be kept on a maintenance program and should be recharged periodically according to the recommendations shown in table 1. Battery packs can be recharged using the UPS (uninterruptible power supply). 

Table 1: Storage Temperature and Supplementary Recharge Intervals

view table

The battery OCV (Open Circuit Voltage) can be used as an indicator of battery pack residual capacity. When measuring the OCV, the battery pack should not have been charged or discharged within the past 24 hours. A supplemental recharge should be performed if the battery pack OCV is 24.6 volts or less when measured at 25ºC (77ºF).

The ACG26BP has a recharge time of 2-hours to 90% present capacity from full discharge. The ACG2500BP has a 4-hour recharge time to 90% present capacity from full discharge.

Charging the UPS Battery

The UPS (uninterruptible power supply) charges its battery when connected to utility power. For best results, charge the battery 4-hours before use of the UPS. It is acceptable to use the UPS (uninterruptible power supply) without first charging the battery, but battery run time may be shorter until the battery fully charges

The UPS is continually creating the AC output from a high voltage DC bus, thus protecting your equipment from surges, spikes, brownouts, blackouts and noise.

This unit is an on-line Power Factor Corrected (PFC), Uninterruptible Power Supply (UPS). This UPS accepts wide range voltage and frequency inputs to allow it to provide clean, reliable AC power to the equipment it supports.

General Maintenance:

Inspection

Ensure the unit is clean with no fluid spills. Do not store anything on the unit.

Cleaning

The 2000 Watt Rugged-UPS product and its accessories are chemically resistant to most common cleaning solutions and non-caustic detergents. The following list includes approved cleaning solutions:

  • 90% Isopropyl alcohol
  • Soap and water
  • Chlorine bleach (30ml/water)

Acumentrics recommends cleaning the UPS unit and cables with a soft damp cloth, and cleaning agents mentioned.

Do NOT immerse any part of the UPS unit in water. Do not use ketones (MEK, acetone, etc). Avoid using abrasives (e.g., paper towels) on the UPS.

For the ACG1250 Series UPS:

Storage and Maintenance of UPS Battery Packs
 

Overview

Proper maintenance and storage is required for lead acid batteries in order to extend the useful life of the battery and prevent potential damage to the UPS (uninterruptible power supply).

Under normal operation, battery maintenance is not required other than periodic checks of the charge status. However, the proper storage of batteries cannot be overemphasized. Improper battery storage is the most common form of battery misuse. All batteries exhibit a loss of charge over time even when stored in an open circuit condition. UPS battery failures can also be caused by storage at elevated temperatures and infrequent recharge of the batteries. UPS batteries placed in storage experience a phenomenon called self-discharge. Both chemical and electrochemical reactions within the battery cause this consumption of the stored energy. Self-discharge is accelerated when the UPS (uninterruptible power supply) batteries are stored at high ambient temperatures, and under these conditions the batteries require more frequent recharge.

Table 1: Storage Temperature and Supplementary Recharge Intervals

UPS batteries placed in storage for extended periods of time must be recharged at the intervals noted below or when the open circuit voltage of the UPS battery pack measures 24.0 VDC.

view table

The battery OCV (Open Circuit Voltage) can be used as an indicator of battery pack residual capacity. When measuring the OCV, the UPS battery pack should not have been charged or discharged within the past 24 hours. A supplemental recharge should be performed if the UPS battery pack OCV is 24.6 volts or less when measured at 25°C (77°F). If the open circuit UPS (uninterruptible power supply) battery pack voltage measures below 23.16 VDC, then permanent battery damage has occurred and the UPS battery pack must be replaced.

Testing

The recommended frequency for testing the UPS Battery Packs is once every 30 days.

The UPS (uninterruptible power supply) battery pack test is performed at ambient room temperature by first measuring the open circuit battery voltage. If the battery voltage measures less than 24.0 VDC, then the battery pack should be replaced. If the battery voltage measures greater than 24.0 VDC, then connect the UPS to a valid AC input (115/230 VAC, 50/60 Hz) source and operate the UPS (uninterruptible power supply) for 24 hours. The UPS should then be powered off and unplugged from the AC source. Remove the battery pack from the UPS. After 24 hours, measure the battery voltage at the pins located at the rear of the battery pack. Table 2, “Battery State of Charge”, defines the condition of the battery having been fully charged by the UPS (uninterruptible power supply). If after 48 hours, the Open Circuit Voltage of the battery is less than 25.7 VDC, then the UPS battery should be replaced.

The battery voltage can also be measured from the comm port when the unit is fully off, provided the comm port is accessible. The comm port is an RS232 compatible interface through a nine-pin D type connector (refer to pin description in question 3). This port provides UPS (uninterruptible power supply) and input power status information to the operator.

Table 2: Battery State of Charge

view table

Specific Information By Model


Front Display ACG1250U, ACG1250Ui, ACG1250U-SH


Front Display ACG1250U-24, ACG1250Ui24, ACG1250-24-SH


ACG1250U, ACG1250U-24, ACG1250Ui, ACG1250Ui24, ACG1250U-SH and ACG1250U-24-SH uninterruptible power supplies do not ship with batteries. There are two optional UPS battery packs that can be used with these units, the ACG26BP and the ACG52BP.


Not all installations will require internal batteries, for example if you have the capability to utilize the external DC connections to the UPS or if you plan to use the UPS as an inverter.
The ACG26BP has a 2-hour recharge time to 90% capacity from full discharge.
The ACG52BP has a 4-hour recharge time to 90% capacity from full discharge.

UPS Run Time Chart:

view table

  • ON/OFF: Powers the UPS as well as turns on\off the audible alarm.
  • AC Input Breaker: Trips when the loads exceed the UPS’s capacity.

LED Display Panel:

  • Battery Status Meter: Displays the present battery charge in volts DC (Range 20 -28 VAC).
  • Load Meter: Displays the power being drawn by the loads (Range 0 - 1000 watts).
  • Overload: This LED lights when the loads connected to the UPS exceed the UPS’s capacity.
  • On Internal DC: The UPS is supplying power to the loads for the internal batteries.
  • Over Temperature: This LED lights when the UPS internal operating temperature has exceeded specifications.
  • On AC: The UPS is supplying power to the loads for the AC connection source.
  • On External DC: The UPS is supplying power to the loads from the external DC connection source.
  • Replace Battery: This LED lights when the battery has reached the end of its usable life.

UPS Batteries and Recycling

The batteries used by this Uninterruptible Power Supply (UPS) are recyclable. Proper disposal of UPS batteries is required. UPS batteries contain lead and pose a hazard to the environment and health if not disposed of properly. Please refer to local codes for proper disposal requirements or return the UPS to a factory-authorized Service Center for battery replacement or disposal.

UPS battery replacement should be performed or supervised by personnel familiar with the danger of batteries and the required precautions. Keep unauthorized personnel away from UPS batteries. When replacing UPS batteries, use the same number and type of sealed lead acid batteries as were originally contained in your UPS (uninterruptible power supply).

Caution - Do not dispose of UPS batteries in fire. The batteries may explode.

Caution - Do not open or mutilate the UPS battery or batteries. They contain an electrolyte that is toxic and harmful to the skin.

Caution - A UPS battery can present a risk of electrical shock and high short circuit current. When replacing UPS batteries, wrist watches and jewelry such as rings should be removed. Use tools with insulated handles.


 

Do you have run-time data for the ACG2500 UPS Units?


 

How do I communicate with Acumentrics' UPS systems?

Acumentrics' UPS systems have two modes of communication, simple signal and smart. The former uses dry contact closures and the latter is true RS-232 communication.

Acumentrics communications cable part number: ACG9236 allows users to utilize the built in UPS monitoring functionality of Windows' operating systems (NOTE: on notebook computers this is not accessible). This Windows UPS monitoring uses our simple signal mode to provide the user notification that AC power has been lost or restored and low battery alerts. RS-232 uses cable part number: ACG9270.


 

Which military standards does Acumentrics' RUPS hold?

Acumentrics' 1000W and 2000W series RUPS have achieved MIL-STD-810G (environmental), MIL-STD-461F (electro-magnetic inference), and MIL-STD-1275D (steady state and transient voltages) certifications.


 

Can Acumentrics' new Lithium Ion battery packs replace the original Lead acid battery packs used in my system?

Yes, Acumentrics' Lithium Ion battery packs are backwards compatible with fielded units.


 

Can you provide me with a copy of my UPS (uninterruptible power supply) Operators Manual?

Acumentrics Operator manuals are available for download here.


 

Can you provide me with instructions for setting up the Parallel UPS units? How do they work?

Acumentrics Operator manuals are available for download here.

Parallel UPS Operation:

Parallel UPS (uninterruptible power supplies) work in a master/slave configuration. All parallel UPS units are identical. The master is determined by the use of the master parallel cable

The master UPS controls the voltage output and the slaves act as current sources. The master UPS supplies the slaves with the command current signal.

The feedback paths in the parallel UPS units are opened internally and closed when properly cabled. If a parallel UPS (uninterruptible power supply) does not have a properly attached parallel connector, it will have an open feedback loop and not be able to react in time to the fault.

The AC Output of each parallel UPS must be hardwired together (no circuit breakers, switches, etc.) to a junction box. After the junction, there can be a switch or circuit breaker.


 

What is the warranty on the UPS units?

• Acumentrics Warranty (pdf).

The shipping material for the UPS (uninterruptible power supply) is designed to provide the necessary protection during shipping. These materials must be used if you ever need to return the UPS for service. Damage sustained during transit is not covered under UPS warranty.


 

What is your UPS repair policy? Where is your UPS repair facility?

 Acumentrics UPS repair facility is located at our factory in Walpole, Massachusetts.

See out contact section and select repair services to contact Acumentrics.

Contact us 


 

How can I obtain a quote for your uninterruptible power supplies?

see how to buy 


 

Can you provide me with a copy of the MSDS/SDS sheet for the battery in my UPS?

MSDS/SDS for small LFP Batteries (360 KB) 
MSDS/SDS for medium LFP Batteries (360 KB) 
MSDS/SDS for Lead Acid Batteries (98 KB) 

 

 

 

Get in touch

Contact us Live chat

Tested to withstand

  • Cold temperature

    Acumentrics Total Power Solutions including the RUPS™ are tested to the most stringent cold temperatures down to -20°C with LFP batteries. For solutions requiring lower temperatures, contact Acumentrics.

    Learn more

  • Hot temperature

    Acumentrics Total Power Solutions are field war zone proven and support very high temperatures with very long life and high reliability with LFP Chemistry up to 60°C. Storage at high temperatures is possible with a very limited effect on battery life.

    Learn more

  • Blown Precipitation

    Our unique heat exchanger Flo-thru™ technology, tunnel design and sealed enclosure provide maximum protection for internal components from damaging effects of blown precipitation and any other contaminants like dust, sand, moisture and others, delivering an unmatched reliability for our RUPS™ in combat zones harsh environment.

    Learn more

  • Shock and vibration

    All our RUPS™ used in communications and electronic power devices are tested and proven with extremely high reliability in combat zone extremely harsh environment for mobile applications with stringent shock and vibration abuse. They have been tested and passed MIL-STD-810G and MIL-S-901-D.

    Learn more

  • Fault tolerant

    Our Rugged Blade UPS™ is designed to support, resilient, fault tolerant, power systems, using an N+1 configuration, when clean power is mission critical. Acumentrics peer to peer relationship between the units with a "moving master, sliding slave" scheme delivers the highest possible reliability with up to 8 units in parallel using a very resilient N+1 Rugged Sync Bus™

    white paper

Total Power Solutions

  • RUPS™
    Acumentrics RUPS 1,000W to 2,400W series RUPS have achieved MIL-STD-810-G (environmental), MIL-STD-461-F (electro-magnetic interference), and MIL-STD-1275-D (steady state and transient voltages) certifications.

    View products

  • PDB and PDU
    The Rugged PDU and Rugged Backplane from Acumentrics eases power distribution, simplifies cabling and offers circular mil-spec connectors sealed with positive latching to protect against rain, wind, dust, blowing sand, humidity, vibration and shock.

    View products

  • Battery Packs, Internal and External modules
    LFP and Lead Acid battery packs provide low maintenance, high run time and enhanced cycle life. Acumentrics External Battery Modules (EBM) increase battery runtime.

    View products

  • Cables & Racks accessories / Cabinets and Transit cases
    Sampling of Acumentrics Rugged UPS accessories. Contact customer services at cs@acumentrics.com or at 844-787-7872 (844-RUPS-USA) to discuss your configuration needs.

    View products

Acumentrics' Products

View

Let's work together

Note: These are available on the ACG2500 Series only. DC output for the ACG1252 Series is 150W.

For Warranty & Repair service, please contact Acumentrics at repairs@acumentrics.com.

To apply to an Acumentrics position, please use the application form.